一、消防滅火系統有哪幾種
消防滅(mie)(mie)(mie)火(huo)系(xi)(xi)統(tong)(tong)(tong)類型一般(ban)分(fen)為:火(huo)災(zai)自(zi)動(dong)報警系(xi)(xi)統(tong)(tong)(tong)、氣體滅(mie)(mie)(mie)火(huo)系(xi)(xi)統(tong)(tong)(tong)、泡沫滅(mie)(mie)(mie)火(huo)系(xi)(xi)統(tong)(tong)(tong)、防排煙系(xi)(xi)統(tong)(tong)(tong)、消防栓(shuan)系(xi)(xi)統(tong)(tong)(tong)、滅(mie)(mie)(mie)火(huo)器配置、自(zi)動(dong)噴水滅(mie)(mie)(mie)火(huo)系(xi)(xi)統(tong)(tong)(tong)、火(huo)災(zai)應急(ji)照明(ming)和疏散指(zhi)示標(biao)志。
這些消防滅火(huo)系統一般都(dou)(dou)用(yong)在住宅(zhai)、配(pei)電室、樓梯(ti)間(jian)、走道(dao)、地(di)下(xia)車(che)庫等建筑(zhu)(zhu)物,幾乎所有建筑(zhu)(zhu)物都(dou)(dou)要安裝(zhuang)。
二、消防滅火系統工作原理是什么
1、自動報警系統的工作原理
火(huo)(huo)(huo)(huo)(huo)災(zai)(zai)自動報(bao)警(jing)(jing)系統應由觸發裝置(zhi)、災(zai)(zai)報(bao)警(jing)(jing)裝置(zhi)、災(zai)(zai)警(jing)(jing)報(bao)裝置(zhi)和電源(yuan)等(deng)四(si)部分組成,火(huo)(huo)(huo)(huo)(huo)災(zai)(zai)報(bao)警(jing)(jing)大致(zhi)過(guo)程:當煙、溫(wen)度(du)、光(guang)(guang)、氣體濃度(du)等(deng)火(huo)(huo)(huo)(huo)(huo)場參數超(chao)過(guo)某一給定閾值時,火(huo)(huo)(huo)(huo)(huo)災(zai)(zai)探(tan)測器(qi)動作,發出(chu)報(bao)警(jing)(jing)號,該信號經過(guo)連接(jie)導線傳送至(zhi)區域(yu)火(huo)(huo)(huo)(huo)(huo)災(zai)(zai)報(bao)警(jing)(jing)控(kong)制器(qi)和(或)集中火(huo)(huo)(huo)(huo)(huo)災(zai)(zai)報(bao)警(jing)(jing)控(kong)制器(qi),發出(chu)聲、光(guang)(guang)報(bao)警(jing)(jing)信號,同時顯示火(huo)(huo)(huo)(huo)(huo)災(zai)(zai)發生的(de)部位,以通(tong)知消防值班人員做出(chu)反(fan)應,這也就是我們通(tong)常所說(shuo)的(de)火(huo)(huo)(huo)(huo)(huo)災(zai)(zai)自動報(bao)警(jing)(jing)系統的(de)工作原理。
2、防排煙系統的工作原理
當發(fa)生災后,操作機(ji)構在煙感報警電信號作用(yong)下,將風閥自(zi)動(dong)(dong)打開,并(bing)啟動(dong)(dong)送風機(ji)與排煙風機(ji),當排煙管內的氣流(liu)達(da)到280°C時,管道防火(huo)閥熔斷器熔斷。關(guan)閉(bi)防火(huo)閥,關(guan)閉(bi)信號通(tong)過輸入模塊發(fa)送至控(kong)制(zhi)(zhi)器,自(zi)動(dong)(dong)或(huo)手(shou)動(dong)(dong)啟動(dong)(dong)相應控(kong)制(zhi)(zhi)模塊去關(guan)閉(bi)排煙機(ji)。
在(zai)有空(kong)(kong)調(diao)設備時,空(kong)(kong)調(diao)送(song)風管道內(nei)的氣流溫(wen)度(du)達到70°C時,防火熔斷器(qi)動(dong)作,關(guan)(guan)閉(bi)(bi)防火閥,關(guan)(guan)閉(bi)(bi)信號通過輸入模(mo)塊(kuai)傳(chuan)送(song)至控(kong)制器(qi),控(kong)制器(qi)則根(gen)據(ju)聯(lian)動(dong)關(guan)(guan)系給控(kong)制模(mo)塊(kuai)信號,關(guan)(guan)閉(bi)(bi)空(kong)(kong)調(diao)機。
3、泡沫系統的工作原理
(1)閉式泡沫噴淋滅火系統工作原理
當有(you)火災發(fa)生時,閉式噴(pen)頭(tou)的玻璃(li)球破裂噴(pen)水(shui),水(shui)流(liu)指(zhi)示器、濕式報警閥(fa)動作,有(you)信(xin)號傳至控制柜(ju),此時,手動或自動開啟消防泵比(bi)例(li)混合裝(zhuang)置上的電磁閥(fa)及管路(lu)閥(fa)門,系(xi)統工(gong)作。一(yi)(yi)定壓力(li)的消防水(shui)經泡(pao)(pao)沫比(bi)例(li)混合裝(zhuang)置與泡(pao)(pao)沫液混合,形成一(yi)(yi)定比(bi)例(li)的泡(pao)(pao)沫混合液,經噴(pen)頭(tou)生成空氣(qi)泡(pao)(pao)沫滅火。
系統組成:閉式(shi)泡(pao)沫(mo)(mo)噴淋滅火系統主要由消防水泵泡(pao)沫(mo)(mo)比例混合裝置(zhi)、閉式(shi)噴頭(tou)、水流指示器(qi)、濕式(shi)報警閥及其它閥門(men)、管道等組成。
(2)開式泡沫噴淋滅火系統的工作原理
當有火(huo)災發生時,安裝于保(bao)護(hu)區的火(huo)災探測(ce)器有信號傳至控制柜,此時,手動或自(zi)動開(kai)啟雨淋(lin)閥(fa)(fa)、消防(fang)泵比(bi)(bi)例混合(he)(he)器上的電磁閥(fa)(fa)及(ji)管路閥(fa)(fa)門,系(xi)統工作。壓力消防(fang)水(shui)經泡(pao)(pao)沫(mo)比(bi)(bi)例混合(he)(he)裝置與泡(pao)(pao)沫(mo)液(ye)混合(he)(he),形(xing)成一(yi)定比(bi)(bi)例的泡(pao)(pao)沫(mo)混合(he)(he)液(ye),經噴頭(tou)生成空氣泡(pao)(pao)沫(mo)滅火(huo)。
系統組成(cheng):開式泡沫噴淋滅火系統主要(yao)由消防水泵、泡沫比例混(hun)合裝置、開式噴頭、雨淋閥及其它閥門、管(guan)道等組成(cheng)。
4、室內外消火栓系統的工作原理
消(xiao)(xiao)火栓(shuan)開啟(qi)(qi)(qi),有(you)水噴出(chu),恒壓泵啟(qi)(qi)(qi)動,恒壓對(dui)管(guan)網(wang)補壓,按下(xia)破玻按鈕(niu),消(xiao)(xiao)防(fang)中(zhong)心收(shou)到(dao)破玻按鈕(niu)報警信號,警鈴鳴響,直接啟(qi)(qi)(qi)動主(zhu)消(xiao)(xiao)防(fang)水泵,消(xiao)(xiao)防(fang)水泵對(dui)管(guan)網(wang)進行加壓,消(xiao)(xiao)火栓(shuan)上的啟(qi)(qi)(qi)泵指示燈(deng)亮。消(xiao)(xiao)防(fang)中(zhong)心收(shou)到(dao)消(xiao)(xiao)防(fang)水泵運(yun)行信號。
因水(shui)泵(beng)(beng)壞或水(shui)池無水(shui)時(shi),消(xiao)防車(che)對水(shui)泵(beng)(beng)接(jie)合器進(jin)行加壓,保(bao)證消(xiao)防系統能(neng)正常運行。(水(shui)泵(beng)(beng)能(neng)手動(dong)(dong)(dong)啟動(dong)(dong)(dong),消(xiao)防中心手動(dong)(dong)(dong)啟動(dong)(dong)(dong)、自動(dong)(dong)(dong)啟動(dong)(dong)(dong))。
5、噴淋自動滅火系統的工作原理
噴(pen)淋(lin)頭達到(dao)(dao)額定(ding)溫度時,玻璃內(nei)的液體發熱膨(peng)脹,玻璃管(guan)破碎,噴(pen)淋(lin)頭噴(pen)水(shui)(shui),水(shui)(shui)流指示器報警(jing),消防(fang)中心(xin)收(shou)到(dao)(dao)報警(jing)信號,力(li)下(xia)降,水(shui)(shui)池(chi)或(huo)恒壓(ya)(ya)泵(beng)補(bu)壓(ya)(ya),濕式(shi)報警(jing)閥動(dong)作(zuo),水(shui)(shui)力(li)警(jing)鐘鳴(ming)響,壓(ya)(ya)力(li)開關報警(jing),消防(fang)中心(xin)收(shou)報警(jing)信號,水(shui)(shui)泵(beng)起泵(beng)加壓(ya)(ya)。消防(fang)中心(xin)收(shou)到(dao)(dao)噴(pen)淋(lin)泵(beng)運行(xing)信號。因水(shui)(shui)泵(beng)壞(huai)或(huo)水(shui)(shui)池(chi)無水(shui)(shui)時,消防(fang)車對水(shui)(shui)泵(beng)接合(he)器進行(xing)加壓(ya)(ya),保證(zheng)消防(fang)系統能正(zheng)常(chang)運行(xing)。(水(shui)(shui)泵(beng)能手(shou)動(dong)啟動(dong),消防(fang)中心(xin)手(shou)動(dong)啟動(dong)、自(zi)動(dong)啟動(dong))。
6、氣體自動滅火系統的工作原理
感(gan)煙或感(gan)溫(wen)(wen)探(tan)測器(qi)任(ren)一報(bao)警(jing),主(zhu)(zhu)機收到(dao)信(xin)號,警(jing)鐘鳴(ming)響(xiang),感(gan)煙與感(gan)溫(wen)(wen)探(tan)測器(qi)同時報(bao)警(jing),主(zhu)(zhu)機收到(dao)信(xin)號,警(jing)鐘鳴(ming)響(xiang),光報(bao)警(jing)器(qi)鳴(ming)響(xiang)。30S后聯動風(feng)閥、停空調(diao)新(xin)(xin)風(feng)機等、啟動氣(qi)體進行滅火(huo)(因誤(wu)報(bao)時在30S內按(an)(an)(an)下門(men)(men)口(kou)或主(zhu)(zhu)機上的(de)急(ji)停按(an)(an)(an)鈕停止放氣(qi))。人員發現火(huo)災(zai)時,直接按(an)(an)(an)下門(men)(men)口(kou)或主(zhu)(zhu)機上的(de)緊急(ji)放氣(qi)按(an)(an)(an)鈕,直接聯動風(feng)閥、停空調(diao)新(xin)(xin)風(feng)機等啟動氣(qi)體進行滅火(huo)。
因主機不能正常啟(qi)動(dong)(dong)氣(qi)(qi)體滅(mie)火時(shi),直(zhi)按用機械啟(qi)動(dong)(dong)氣(qi)(qi)體進行滅(mie)火。
7、防火卷簾的工作原理
在火(huo)(huo)災發(fa)生時起防火(huo)(huo)分區隔(ge)斷(duan)作用,在火(huo)(huo)災發(fa)生時,感(gan)(gan)煙探測器(qi)報警(jing),災信號送(song)到卷(juan)簾門(men)(men)制柜,控制柜發(fa)出啟動信號,卷(juan)簾門(men)(men)自(zi)動降到距地1。8米的位(wei)置(特殊部位(wei)的卷(juan)簾門(men)(men)也可一步到底(di)),如果感(gan)(gan)溫探測器(qi)再報警(jing),卷(juan)簾門(men)(men)才降到底(di)。報警(jing)狀態時,人員(yuan)可手動按(an)住上行按(an)鈕升(sheng)起卷(juan)簾,人過(guo)去后放開按(an)鈕后防火(huo)(huo)門(men)(men)又(you)自(zi)動下(xia)行。
8、消防廣播的工作原理
當火災發(fa)生時,災區域/層(如n層)的消防(fang)煙感(gan)溫感(gan)等探測器(qi)發(fa)出報警動(dong)(dong)(dong)作信號,消防(fang)接收控(kong)制(zhi)盤、邏輯控(kong)制(zhi)等消防(fang)聯動(dong)(dong)(dong)裝置自動(dong)(dong)(dong)(或手動(dong)(dong)(dong))啟動(dong)(dong)(dong),通過消防(fang)發(fa)送控(kong)制(zhi)盤發(fa)出驅動(dong)(dong)(dong)和切(qie)換控(kong)制(zhi)信號。
一路去(qu)啟動消防(fang)廣播錄放盤,該盤可(ke)選擇(ze)播音(yin)卡播音(yin)或話筒播音(yin)作為緊急廣播,并可(ke)自(zi)動錄音(yin)。
9、恒壓泵的工作原理
當(dang)管網泄漏、系統(tong)壓(ya)(ya)力降至(zhi)設定壓(ya)(ya)力下限時(shi)(shi),穩壓(ya)(ya)水(shui)泵(beng)(beng)自動(dong)啟動(dong),對管網進行補壓(ya)(ya),以供(gong)消防供(gong)水(shui)系統(tong)保證(zheng)最不利點的(de)消防所(suo)需(xu)壓(ya)(ya)力,當(dang)系統(tong)壓(ya)(ya)力達到設定壓(ya)(ya)力上限時(shi)(shi)穩泵(beng)(beng)停止工作,每(mei)次壓(ya)(ya)力下降時(shi)(shi),都重復上述遠行過程(cheng),以穩定消防管網的(de)壓(ya)(ya)力。
消(xiao)(xiao)防(fang)用水時(shi)(shi),穩壓泵(beng)持(chi)續(xu)運行阻(zu)懷壓力(li)(li)的(de)下(xia)降(jiang),當力(li)(li)降(jiang)到(dao)消(xiao)(xiao)防(fang)主泵(beng)啟(qi)動(dong)壓力(li)(li)時(shi)(shi),電控系(xi)統(tong)發(fa)出(chu)報警(jing)信(xin)號,啟(qi)動(dong)消(xiao)(xiao)防(fang)主泵(beng)進行供水,當消(xiao)(xiao)防(fang)主泵(beng)運行到(dao)達額定流量種(zhong)壓力(li)(li)時(shi)(shi),控制(zhi)系(xi)統(tong)關閉主泵(beng)穩壓水運行,當單臺消(xiao)(xiao)防(fang)泵(beng)運行機(ji)制(zhi)信(xin)用證(zheng)阻(zu)止不住壓力(li)(li)下(xia)降(jiang),系(xi)統(tong)壓力(li)(li)降(jiang)至消(xiao)(xiao)防(fang)最低壓力(li)(li)時(shi)(shi),消(xiao)(xiao)防(fang)備用泵(beng)啟(qi)動(dong)(有兩主一備時(shi)(shi))。