1、定期(qi)巡視檢(jian)測通(tong)信電(dian)源(yuan)設(she)備。注意(yi)機房環境(jing)溫度和設(she)備運行(xing)狀況,利用通(tong)信電(dian)源(yuan)監控系統,實(shi)時(shi)監控通(tong)信電(dian)源(yuan)設(she)備的各種運行(xing)參(can)數,發現問題(ti)及時(shi)處理。
2、電(dian)(dian)(dian)源巡(xun)視檢測內容(rong)。模塊配(pei)置是(shi)否(fou)合理;充(chong)電(dian)(dian)(dian)限流(liu)(liu)(liu)(liu)(liu)值是(shi)否(fou)正確、有無(wu)告警(jing);系統交(jiao)流(liu)(liu)(liu)(liu)(liu)電(dian)(dian)(dian)壓、電(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu),直流(liu)(liu)(liu)(liu)(liu)浮(fu)充(chong)電(dian)(dian)(dian)壓、負載電(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)、蓄電(dian)(dian)(dian)池補充(chong)電(dian)(dian)(dian)電(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)、風扇運(yun)行(xing)狀況(kuang)和(he)防(fang)雷器件(jian)狀況(kuang);監控模塊的(de)各項運(yun)行(xing)參數是(shi)否(fou)正確;溫度(du)補償是(shi)否(fou)正常啟用;模塊均(jun)流(liu)(liu)(liu)(liu)(liu)是(shi)否(fou)小于5%;蓄電(dian)(dian)(dian)池保險和(he)連接條(tiao)溫升;蓄電(dian)(dian)(dian)池是(shi)否(fou)爬酸(suan)、漏液、鼓(gu)肚等現象;機房環境溫度(du)等。
3、利(li)用電源監(jian)控(kong)系(xi)統對(dui)電源設備實時(shi)遠程(cheng)監(jian)控(kong),了解故障現(xian)象,進行遠程(cheng)監(jian)控(kong)解決(jue),協(xie)助現(xian)場處(chu)理(li)(li)。處(chu)理(li)(li)電源設備障礙時(shi),應(ying)首先初步判斷造成電源障礙原因和故障部位,然后(hou)采取相應(ying)的方法和措施對(dui)電源故障進行處(chu)理(li)(li)。
4、在處理故障的(de)過程中(zhong)應重點關(guan)注以下幾方面問題:
(1)一定要(yao)注意不能(neng)引(yin)起直流輸出、交(jiao)流輸入的短(duan)路,各種維護工具必須做好絕(jue)緣處理,確保人身安全(quan)和電源設備(bei)供(gong)電的安全(quan)。
(2)在操作(zuo)時應盡量單手操作(zuo),操作(zuo)時手上、身上不(bu)允許帶有金屬導體的(de)飾品,例如手表、鑰匙、戒(jie)指等,同(tong)時穿上絕緣鞋進(jin)行電源設備維(wei)修。
(3)在處理(li)電(dian)源(yuan)障礙的(de)過程中(zhong),尤(you)其(qi)是小系統電(dian)源(yuan)設(she)備的(de)二次(ci)下電(dian)功能一定要(yao)暫時取消,防(fang)止誤操作(zuo)引起通信電(dian)源(yuan)系統的(de)供電(dian)中(zhong)斷。
(4)在(zai)對(dui)交、直(zhi)流配(pei)電(dian)系統不了解的(de)情況(kuang)下,不要隨意或憑直(zhi)覺打開(kai)(kai)或關(guan)閉交流供電(dian)開(kai)(kai)關(guan),更不允許插、拔直(zhi)流熔斷器和關(guan)掉直(zhi)流輸出空氣開(kai)(kai)關(guan)。