1、定期巡(xun)視檢測(ce)通信電(dian)源設備(bei)。注意機房環境(jing)溫度和設備(bei)運(yun)行(xing)狀況,利用通信電(dian)源監控(kong)系統,實時(shi)監控(kong)通信電(dian)源設備(bei)的各(ge)種運(yun)行(xing)參數,發現問題(ti)及(ji)時(shi)處理。
2、電(dian)(dian)(dian)(dian)源巡(xun)視檢(jian)測(ce)內容。模(mo)塊配置是否(fou)合理(li);充(chong)電(dian)(dian)(dian)(dian)限流(liu)(liu)(liu)值是否(fou)正確、有無告警;系統交流(liu)(liu)(liu)電(dian)(dian)(dian)(dian)壓(ya)、電(dian)(dian)(dian)(dian)流(liu)(liu)(liu),直流(liu)(liu)(liu)浮充(chong)電(dian)(dian)(dian)(dian)壓(ya)、負載電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)、蓄(xu)電(dian)(dian)(dian)(dian)池(chi)補(bu)充(chong)電(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)、風扇運行狀況(kuang)和防(fang)雷器件狀況(kuang);監控模(mo)塊的各(ge)項運行參(can)數是否(fou)正確;溫度(du)補(bu)償是否(fou)正常啟用(yong);模(mo)塊均(jun)流(liu)(liu)(liu)是否(fou)小于5%;蓄(xu)電(dian)(dian)(dian)(dian)池(chi)保險和連接條溫升;蓄(xu)電(dian)(dian)(dian)(dian)池(chi)是否(fou)爬酸、漏(lou)液、鼓肚等(deng)現象(xiang);機房(fang)環境溫度(du)等(deng)。
3、利用電(dian)源監控(kong)系統對電(dian)源設備實時遠程(cheng)監控(kong),了解故障現(xian)象,進行遠程(cheng)監控(kong)解決,協(xie)助現(xian)場處(chu)(chu)理(li)。處(chu)(chu)理(li)電(dian)源設備障礙時,應(ying)首先初步判(pan)斷造成電(dian)源障礙原因和(he)故障部位,然后采(cai)取相(xiang)應(ying)的方法(fa)和(he)措施(shi)對電(dian)源故障進行處(chu)(chu)理(li)。
4、在(zai)處理故障的過程中應重點關(guan)注以(yi)下(xia)幾(ji)方(fang)面問題:
(1)一定要注意不能引起直流輸出、交流輸入的(de)短路,各種維護工具(ju)必(bi)須做好絕緣(yuan)處理,確保人身安(an)全和電源(yuan)設備供電的(de)安(an)全。
(2)在操作(zuo)時應盡量(liang)單手操作(zuo),操作(zuo)時手上(shang)、身(shen)上(shang)不允許帶有金屬(shu)導體的飾品(pin),例如(ru)手表、鑰(yao)匙(chi)、戒指(zhi)等,同時穿上(shang)絕緣鞋進行電源設(she)備維(wei)修。
(3)在處理(li)電(dian)源障礙的(de)過程中(zhong),尤其是小系統電(dian)源設備的(de)二次下電(dian)功能一定要暫時取(qu)消,防止誤操作引起通信(xin)電(dian)源系統的(de)供電(dian)中(zhong)斷(duan)。
(4)在對(dui)交(jiao)、直(zhi)(zhi)流配電(dian)系統不(bu)了(le)解的(de)情況下(xia),不(bu)要隨意(yi)或憑(ping)直(zhi)(zhi)覺(jue)打開(kai)(kai)或關(guan)閉(bi)交(jiao)流供電(dian)開(kai)(kai)關(guan),更不(bu)允許插、拔直(zhi)(zhi)流熔斷器和關(guan)掉直(zhi)(zhi)流輸出空(kong)氣(qi)開(kai)(kai)關(guan)。