通(tong)常(chang)(chang)用普通(tong)電(dian)(dian)(dian)流表測(ce)量電(dian)(dian)(dian)流時,需(xu)要將電(dian)(dian)(dian)路切(qie)斷停機后(hou)才能將電(dian)(dian)(dian)流表接入(ru)進(jin)行測(ce)量,這是(shi)很麻煩的(de)(de),有(you)時正常(chang)(chang)運(yun)行的(de)(de)電(dian)(dian)(dian)動機不(bu)允許這樣做(zuo)。此(ci)時,使用鉗形電(dian)(dian)(dian)流表就顯得方便多了,可以(yi)在不(bu)切(qie)斷電(dian)(dian)(dian)路的(de)(de)情況下來測(ce)量電(dian)(dian)(dian)流。
穿過(guo)鐵心的(de)被測(ce)(ce)電(dian)路(lu)導線就成為電(dian)流(liu)互感器的(de)一次線圈,其中通過(guo)電(dian)流(liu)便(bian)在二次線圈中感應出(chu)電(dian)流(liu)。從(cong)而使二次線圈相連接的(de)電(dian)流(liu)表(biao)(biao)便(bian)有(you)(you)指示-----測(ce)(ce)出(chu)被測(ce)(ce)線路(lu)的(de)電(dian)流(liu)。鉗形表(biao)(biao)可以通過(guo)轉換(huan)開關(guan)的(de)撥檔,改換(huan)不同(tong)的(de)量程(cheng)(cheng)。但撥檔時不允許帶(dai)電(dian)進行操作。鉗形表(biao)(biao)一般準確度不高,通常為2.5~5級。為了(le)使用方便(bian),表(biao)(biao)內還有(you)(you)不同(tong)量程(cheng)(cheng)的(de)轉換(huan)開關(guan)供測(ce)(ce)不同(tong)等級電(dian)流(liu)以及(ji)測(ce)(ce)量電(dian)壓(ya)的(de)功(gong)能。
小巧輕便(bian)的鉗形(xing)表。
40A/400AAC/DC
400V/600VAC,DC
電阻/蜂鳴功能(neng)。
自動關機功能。
數據保持功能。
最大顯示4000計數。
自動回零功能。
設(she)計符合(he)國際安全規(gui)格IEC61010-1CAT.III300V
用鉗(qian)形(xing)電(dian)(dian)流(liu)表檢(jian)測(ce)(ce)電(dian)(dian)流(liu)時(shi),一(yi)定要夾入一(yi)根被測(ce)(ce)導(dao)線(xian)(電(dian)(dian)線(xian)).夾入兩根(平行線(xian))則(ze)不能(neng)檢(jian)測(ce)(ce)電(dian)(dian)流(liu).另外,使(shi)用鉗(qian)形(xing)電(dian)(dian)流(liu)表中心(鐵心)檢(jian)測(ce)(ce)時(shi),檢(jian)測(ce)(ce)誤差小.在(zai)檢(jian)查家電(dian)(dian)產品的(de)耗電(dian)(dian)量(liang)時(shi),使(shi)用線(xian)路分離器比較(jiao)方(fang)便(bian),有(you)的(de)線(xian)路分離器可(ke)將(jiang)檢(jian)測(ce)(ce)電(dian)(dian)流(liu)放(fang)大10倍(bei),因此(ci)1A以下的(de)電(dian)(dian)流(liu)可(ke)放(fang)大后再檢(jian)測(ce)(ce).用直流(liu)鉗(qian)形(xing)電(dian)(dian)流(liu)表檢(jian)測(ce)(ce)直流(liu)電(dian)(dian)流(liu)(DCA)時(shi),如果電(dian)(dian)流(liu)的(de)流(liu)向相反,則(ze)顯示(shi)出負(fu)數.可(ke)使(shi)用該功能(neng)檢(jian)測(ce)(ce)汽車的(de)蓄(xu)電(dian)(dian)池(chi)是充電(dian)(dian)狀態(tai)還是放(fang)電(dian)(dian)狀態(tai).
平均值(zhi)(zhi)方式的(de)鉗形(xing)(xing)電流表通(tong)過交流檢(jian)(jian)測(ce),檢(jian)(jian)測(ce)正弦(xian)波(bo)(bo)(bo)的(de)平均值(zhi)(zhi),并將放大1.11倍(正弦(xian)波(bo)(bo)(bo)交流)之后的(de)值(zhi)(zhi)作為有效(xiao)(xiao)值(zhi)(zhi)顯示出(chu)來.波(bo)(bo)(bo)形(xing)(xing)率(lv)不同(tong)的(de)正弦(xian)波(bo)(bo)(bo)以(yi)外的(de)波(bo)(bo)(bo)形(xing)(xing)和歪(wai)波(bo)(bo)(bo)也同(tong)樣放大1.11倍后顯示出(chu)來,所(suo)以(yi)會產生指(zhi)示誤差.因此檢(jian)(jian)測(ce)正弦(xian)波(bo)(bo)(bo)以(yi)外的(de)波(bo)(bo)(bo)形(xing)(xing)和歪(wai)波(bo)(bo)(bo)時(shi),請選(xuan)用可(ke)直接測(ce)試出(chu)真有效(xiao)(xiao)值(zhi)(zhi)的(de)鉗形(xing)(xing)電流表.
漏(lou)電(dian)(dian)(dian)(dian)檢(jian)(jian)測(ce)(ce)與通常的(de)電(dian)(dian)(dian)(dian)流(liu)(liu)檢(jian)(jian)測(ce)(ce)不同,兩根(單(dan)相(xiang)2線(xian)(xian)式(shi))或(huo)三根(單(dan)相(xiang)3線(xian)(xian)式(shi),三相(xiang)3線(xian)(xian)式(shi))要全部夾住(zhu)。也可夾住(zhu)接地線(xian)(xian)進行(xing)檢(jian)(jian)測(ce)(ce).在(zai)低壓電(dian)(dian)(dian)(dian)路(lu)上(shang)檢(jian)(jian)測(ce)(ce)漏(lou)電(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)流(liu)(liu)的(de)絕緣管(guan)理方(fang)法,已成為首(shou)要的(de)判斷手段.自(zi)其(qi)被(1997年電(dian)(dian)(dian)(dian)氣設(she)備技術標準(zhun)的(de)修正)確認以(yi)來,在(zai)不能停電(dian)(dian)(dian)(dian)的(de)樓(lou)宇和工廠,便逐漸采用漏(lou)電(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)流(liu)(liu)鉗表來檢(jian)(jian)測(ce)(ce).
①進行電流測(ce)量時(shi),被測(ce)載流體的位置(zhi)應放在鉗(qian)口中央,以免產生誤差。
②測量(liang)前應估計被測電(dian)流(liu)的大小(xiao),選擇合適的量(liang)程(cheng),在(zai)不知道電(dian)流(liu)大小(xiao)時,應選擇最大量(liang)程(cheng),再根據指(zhi)針(zhen)適當減小(xiao)量(liang)程(cheng),但不能(neng)在(zai)測量(liang)時轉換量(liang)程(cheng)。
③為了使讀數準確(que),應(ying)保持鉗口干凈(jing)(jing)無損,如(ru)有污垢(gou)時,應(ying)用汽(qi)油擦洗干凈(jing)(jing)再進行測量。
④在測量5A以下的電(dian)流時,為了測量準確(que),應該繞圈測量。
⑤鉗(qian)形表不能測量裸(luo)導線(xian)電流,以防觸電和(he)短路。
⑥測量(liang)完(wan)后一定要將量(liang)程(cheng)分檔旋(xuan)鈕放到(dao)最大量(liang)程(cheng)位(wei)置上。